CONTROLLER
46 | MVE User Manual (710-17074-00G)
16C
Undercurrent
16D
Instantaneous Overcurrent
16E
Current Imbalance
16F
Frequency
16G
Input A Trip
16H
Input B Trip
16I
Motor Thermistor
16J
Starter Communication
16K
Network Communication
16L
Reserved
16M
Battery/Clock
16N
Ground Fault
16O
Reserved
16P
Reserved
16Q
Reserved
16R
Reserved
16S
Reserved
16T
Reserved
16U
Reserved
7.15 Parameter Descriptions
1 Motor Data-1
The parameters in Motor Data-1 configure the soft starter to match the connected motor. These parameters describe the motor's
operating characteristics and allow the soft starter to model the motor's temperature.
5 - 1200 A
100 A
Matches the starter to the connected motor's full load current. Set to the full load current (FLC) rating shown
on the motor nameplate.
1B – Locked Rotor Time
Range:
0:01 - 2:00 (minutes:seconds)
10 seconds
Sets the maximum length of time the motor can sustain locked rotor current from cold before reaching its
maximum temperature. Set according to the motor datasheet.
1C – Locked Rotor Current
Range:
400% - 800% FLC
600%
Sets the locked rotor current of the connected motor, as a percentage of full load current. Set according to the
motor datasheet.
1D – Motor Service Factor
Range:
100% - 120%
105%
Sets the motor service factor used by the thermal model. If the motor runs at full load current, it will reach
100%. Set according to the motor datasheet.
2 Start/Stop Modes-1
Constant Current (default)
Selects the soft start mode.