CONTROLLER
46 | MVE User Manual (710-17074-00G)
16C
Undercurrent
16D
Instantaneous Overcurrent
16E
Current Imbalance
16F
Frequency
16G
Input A Trip
16H
Input B Trip
16I
Motor Thermistor
16J
Starter Communication
16K
Network Communication
16L
Reserved
16M
Battery/Clock
16N
Ground Fault
16O
Reserved
16P
Reserved
16Q
Reserved
16R
Reserved
16S
Reserved
16T
Reserved
16U
Reserved
16V
Undervoltage
16W
Overvoltage
7.15 Parameter Descriptions
1 Motor Data-1
The parameters in Motor Data-1 configure the soft starter to match the connected motor. These parameters describe the motor's
operating characteristics and allow the soft starter to model the motor's temperature.
1A Motor FLC
Range:
5 - 1200 A
Default:
100 A
Description:
Matches the starter to the connected motor's full load current. Set to the full load current (FLC) rating shown
on the motor nameplate.
1B Locked Rotor Time
Range:
0:01 - 2:00 (minutes:seconds)
Default:
10 seconds
Description:
Sets the maximum length of time the motor can sustain locked rotor current from cold before reaching its
maximum temperature. Set according to the motor datasheet.
1C Locked Rotor Current
Range:
400% - 800% FLC
Default:
600%
Description:
Sets the locked rotor current of the connected motor, as a percentage of full load current. Set according to the
motor datasheet.
1D Motor Service Factor
Range:
100% - 120%
Default:
105%
Description:
Sets the motor service factor used by the thermal model. If the motor runs at full load current, it will reach
100%. Set according to the motor datasheet.
2 Start/Stop Modes-1
2A Start Mode
Options:
Constant Current (default)
Description:
Selects the soft start mode.