CONTROLLER
58 | MVE User Manual (710-17074-00G)
9A ~ 9E – Secondary Motor Settings
Parameter 9A
Reserved
This parameter is reserved for future use.
Parameter 9B
Motor FLC-2
5 - 1000 A
100 A
Sets the secondary motor's full load current.
Parameter 9C
Reserved
This parameter is reserved for future use.
Parameter 9D
Reserved
This parameter is reserved for future use.
Parameter 9E
Reserved
This parameter is reserved for future use.
10 Start/Stop-2
Refer to Start/Stop-1 (parameters 2A~2I) for details.
Parameter 10A
Start Mode-2
Constant Current (default)
Selects the soft start mode.
Parameter 10B
Start Ramp-2
0:01 - 3.00 (minutes:seconds)
1 second
Sets the ramp time for current ramp starting (from the initial current to the current limit).
Parameter 10C
Initial Current-2
50% - 600%
400%
Sets the initial start current level for current ramp starting, as a percentage of motor full load current. Set so
that the motor begins to accelerate immediately after a start is initiated.
If current ramp starting is not required, set the initial current equal to the current limit.
Parameter 10D
Current Limit-2
50% - 600% FLC
400%
Sets the current limit for constant current and current ramp soft starting, as a percentage of motor full load
current.
Parameter 10E
Reserved
This parameter is reserved for future use.
Parameter 10F
Kickstart Time-2
0 - 2000 (milliseconds)
0000 milliseconds
Sets the kickstart duration. A setting of 0 disables kickstart.
Parameter 10G
Kickstart Level-2
100% - 700% FLC
500%
Sets the level of the kickstart current.
Parameter 10H
Stop Mode-2
Coast To Stop (default)
TVR Soft Stop
Selects the stop mode.
Parameter 10I
Stop Time-2
0:00 - 4:00 (minutes:seconds)
0 second
Sets the stop time.