CONTROLLER
60 | MVE User Manual (710-17074-00G)
Continued use of Emergency Run is not recommended. Emergency Run may compromise the starter life as all
protections and trips are disabled.
Using the starter in 'Emergency Run' mode will void the product warranty.
16 Protection Action
These parameters define how the soft starter will respond to different protection events. The soft starter can trip, issue a warning,
or ignore different protection events as required. All protection events are written to the event log. The default action for all
protections is to trip the soft starter.
Defeating the protection may compromise the starter and motor, and should only be done in the case of emergency.
16A~16W – Protection Actions
Options:
Trip Starter (default)
Warn and Log
Log Only
Selects the soft starter's response to each protection.
• 16A
Motor Overload
• 16B
Excess Start Time
• 16C
Undercurrent
• 16D
Instantaneous Overcurrent
• 16E
Current Imbalance
• 16F
Frequency
• 16G
Input A Trip
• 16H
Input B Trip
• 16I
Motor Thermistor
• 16J
Starter Communication
• 16K
Network Communication
• 16L
Reserved
• 16M
Battery/Clock
• 16N
Ground Fault
• 16O~16U
Reserved
• 16V
Undervoltage
• 16W
Overvoltage
20 Restricted
These parameters are restricted for Factory use and are not available to the user.