Application
Parking frame for safe storage of a disconnected plug or cover.
For protection against touching the bare contacts and against environmental
influences.
5.3.3. DS intermediate frame for double sealing
Figure 30: Electrical connection with DS intermediate frame
[1] Electrical connection
[2] DS intermediate frame
Application
When removing the electrical connection or due to leaky cable glands, there is a
potential risk of ingress of dust and water into the housing.This is prevented
effectively by inserting the double sealed intermediate frame [2] between the
plug/socket connector [1] and the housing of the device.The enclosure protection
of the device (IP68) will not be affected, even if the electrical connection [1] is
removed.
5.3.4. External earth connection
Figure 31: Earth connection for multi-turn actuator
Application
External earth connection (U-bracket) for connection to equipotential compensation.
Table 15:
Terminal cross sections and earth connection tightening torques
Tightening torquesTerminal cross sectionsConductor type
3 – 4 Nm2.5 mm² to 6 mm²Solid wire and stranded
3 – 4 Nm1.5 mm² to 4 mm²Fine stranded
For fine stranded (flexible) wires, connection is made via cable lugs/ring terminals. When connecting
two individual wires with a U-bracket, cross sections have to be identical.
34
SAV 07.2 – SAV 16.2 / SARV 07.2 – SARV 16.2 Control unit: electronic (MWG)
Electrical connection ACV 01.2 Modbus TCP/IP