11.
Press .
➥
Display indicates:
ENTER PASSWORD
0 * * *
:EDIT :OK C:ESC
12. Enter password:
→
Press
4 x = 0000 (default factory password).
➥
EDIT M1110
OPEN POSITION
CLOSED POSITION
EDIT M1111
OPEN POSITION
CLOSED POSITION
Use and to select between OPEN POSITION and CLOSED POSITION.
13.
Press .
➥
Display shows the set value:
EDIT M1110
OPEN POSITION
LIMIT
↵
:EDIT C:ESC
EDIT M1111
CLOSED POSITION
LIMIT
:EDIT C:ESC
Use and to select between OPEN POSITION and CLOSED POSITION.
14.
Press
again to enter the edit mode.
➥
Display indicates:
EDIT M1110
OPEN POSITION
LIMIT
:EDIT :OK C:ESC
EDIT M1111
CLOSED POSITION
LIMIT
:EDIT :OK C:ESC
15. Set new value:
→
Press .
43
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTU Commissioning (basic settings)