Table 7: Standard operating temperature
Standard operating temperature Specifications
Continuous operation (for altitude less than
950 m or 3117 ft)
5°C–40°C (41°F–104°F) with no direct sunlight on the
equipment.
Power requirements
The system supports up to two AC power supply units (PSU).
Table 8: PSU specifications
PSU Class Heat dissipation
(maximum)
Frequency Voltage
750 W AC Platinum 2891 BTU/hr 50/60 Hz 100–240 V AC, autoranging
Table 9: ACP 100 Series - Dell R640 Power Requirements
ACP100 Series Dell R640 System VA rating Heat Output (BTU/hr) Peak Power Max.
(Watts)
Profile 2 200 680 270
Profile 3 340 1161 457
Profile 4 283 1066 365
Profile 5 504 1721 655
Profile 51 528 1802 685
Power requirements
October 2019 Installing the Avaya Converged Platform 130 Series 19