EasyManua.ls Logo

AVS Electronics OUTSPIDER DT - SW1 - FUNCTIONS; INFRARED SECTION CONFIGURATION; MICROWAVE SECTION CONFIGURATION (only OUTSPIDER DT); SENSOR OPERATION (only OUTSPIDER DT)

AVS Electronics OUTSPIDER DT
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 36 -
SW1 - FUNCTIONS
In operation with relays, the configurations that can be programmed with the Dip Switch SW1 strip are:
INFRARED SECTION CONFIGURATION
DIP 1 OFF DEFAULT In this configuration, the infrared section has a default sensitivity (studied
for standard use) and executes a digital analysis of the signals.
DIP 2 OFF
DIP 1 ON
LOW in this configuration, the infrared section has a low sensitivity compared
to the default and executes a digital analysis of the signals which is
more severe than the default one and considers a dual impulse.
DIP 2 OFF
DIP 1 OFF
MEDIUM in this configuration, the infrared section has a medium sensitivity
compared to the default and executes a digital analysis of the signals
which is more severe than the default one.
DIP 2 ON
DIP 1 ON HIGH
in this configurations, the sensor has a high sensitivity and detects any
signal analysing amplitude and frequency.
DIP 2 ON
MICROWAVE SECTION CONFIGURATION (only OUTSPIDER DT)
DIP 3 OFF DEFAULT in this configuration, the microwave section executes a digital analysis
of the signal.
DIP 4 OFF
DIP 3 ON APPROACHING in this configuration, the microwave section analyses the signal while
considering only the movements approaching the sensor
DIP 4 OFF
DIP 3 OFF MOVING AWAY in this configuration, the microwave section analyses the signal while
considering only the movements moving away from the sensor
DIP 4 ON
DIP 3 ON NO CONTROL in this configuration, the microwave section detects any movement while
analysing the intensity and frequency of the signal.
DIP 4 ON
SENSOR OPERATION (only OUTSPIDER DT)
DIP 5
OFF
AND the alarm is generated only when both sections (infrared and microwave)
detect the adequate signal
ON
SECURITY
(not recommended for
external use)
the sensor works in OR integrated; it therefore generates an alarm signal
even when the individual section detects a series of valid signals
DIP 6 NOT USED
DIP 7 NOT USED
DIP 8 NOT USED
NOTE: by default, the DIP SWITCHES are all positioned at OFF
The DIP SWITCH of the SW 1 strip
change usage function based on
operational mode se in the sensor (DIP
1 of the SW 2 strip):
DIP/RELAY mode: in this mode the DIP
SWITCHES are used to configure
operation of the two section (infrared
and microwave) as shown on the table
at the side.
PC/BUS mode: in this mode the DIP
SWITCHES are used to assign an
address to the sensor (see table on the
next page).
However, even in PC/BUS Mode is is
possible temporarily use DIP
SWITCHES from SW 1 to configure the
two sections as if the DIP/RELAY Mode
was selected.
In order to do this, it is sufficient to:
1. Set the DIP SWITCH according to
the desired configuration.
2. Position DIP SWITCH 1 of SW 2
in the ON position.
3. Bring DIP SWITCH 1 of SW 2 to
the OFF position.
4. Position the DIP SWITCH of the
SW 1 based on the address to be
assigned to the sensor.
E
N
G

Table of Contents

Related product manuals