9-3
Chapter 9. LIST OF COMMUNICATION DATA
Bank
Item name
RAM address EEPROM address RAM EEPROM
Decimal
point
information
Notes
Decimal
Hexadecimal
Decimal
Hexadecimal
Read Write Read Write
Setup
Auxiliary output scaling low limit
5254 1486 21638 5486 S
Auxiliary output scaling high limit
5255 1487 21639 5487 S
Auxiliary output MV scalable
bandwidth
5256 1488 21640 5488 P
(Note 2)
Position proportional type
5257 1489 21641 5489
* *
Position proportional control dead zone
5258 148A 21642 548A
* *
1
Motor long life mode
5259 148B 21643 548B
* *
Motor adjust
5260 148C 21644 548C
* *
Input with motor fully closed
5261 148D 21645 548D
* *
Input with motor fully open
5262 148E 21646 548E
* *
Motor full close-full open time
5263 148F 21647 548F
* *
1
Communication type
5264 1490 21648 5490 X X
Station address
5265 1491 21649 5491 X X
Transmission speed
5266 1492 21650 5492 X X
Data format (Data length)
5267 1493 21651 5493 X X
Data format (Parity)
5268 1494 21652 5494 X X
Data format (Stop bit)
5269 1495 21653 5495 X X
Communication minimum response
time
5270 1496 21654 5496 X X
Key operation type
5271 1497 21655 5497
[mode] key function
5272 1498 21656 5498
MODE display setup
5273 1499 21657 5499
PV/SP display setup
5274 149A 21658 549A
MV display setup
5275 149B 21659 549B
Event setting value display setup
5276 149C 21660 549C
Event remaining time display setup
5277 149D 21661 549D
CT input current value display setup
5278 149E 21662 549E
User level
5279 149F 21663 549F
LED monitor
5280 14A0 21664 54A0
MS indicating lamp ON condition
(1st priority)
5281 14A1 21665 54A1
MS indicating lamp ON status
(1st priority)
5282 14A2 21666 54A2
MS indicating lamp ON condition
(2nd priority)
5283 14A3 21667 54A3
MS indicating lamp ON status
(2nd priority)
5284 14A4 21668 54A4
MS indicating lamp ON condition
(3rd priority)
5285 14A5 21669 54A5
MS indicating lamp ON status
(3rd priority)
5286 14A6 21670 54A6
MS indicating lamp deviation range
5287 14A7 21671 54A7
Special function
5288 14A8 21672 54A8 X
Zener barrier adjustment
5289 14A9 21673 54A9 X X
CT1 turns
5290 14AA 21674 54AA
(Note 2)
Number of CT1 power wire loops
5291 14AB 21675 54AB
(Note 2)
CT2 turns
5292 14AC 21676 54AC
(Note 2)
Number of CT2 power wire loops
5293 14AD 21677 54AD
(Note 2)
PV input failure (under range) type
5297 14B1 21681 54B1
(Note 1)
DI
Assignment
Internal Contact 1 Operation type
5401 1519 21785 5519
Internal Contact 1 Input bit operation
5402 151A 21786 551A
Internal Contact 1 Input assignment A
5403 151B 21787 551B
Internal Contact 1 Input assignment B
5404 151C 21788 551C
Internal Contact 1 Input assignment C
5405 151D 21789 551D
Internal Contact 1 Input assignment D
5406 151E 21790 551E
(Continue on next page.)
(Note 1) If ROM version 1 in the instrument information bank (
I
d02
) is 2.26 or earlier,
write accessibility is X and read accessibility is ∆.
(Note 2) If ROM version 1 in the instrument information bank (
I
d02
) is 2.04 or earlier, this item is reserved for
future extension, write accessibility is X and read accessibility is ∆ for both RAM and EEPROM.

Table of Contents

Other manuals for Azbil SDC36

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Azbil SDC36 and is the answer not in the manual?

Azbil SDC36 Specifications

General IconGeneral
BrandAzbil
ModelSDC36
CategoryController
LanguageEnglish

Related product manuals