9-11
Chapter 9. LIST OF COMMUNICATION DATA
Bank
Item name
RAM address EEPROM address RAM EEPROM
Decimal
point
information
Notes
Decimal
Hexadecimal
Decimal
Hexadecimal
Read Write Read Write
Operation
display
Manipulated Variable (MV)
9105 2391 25489 6391 * * 1
Same as RAM address 14594
(decimal). Writing is enabled in
the MANUAL mode.
Heat Manipulated Variable (Heat MV)
9106 2392 25490 6392 X X 1
Same as RAM address 14420
(decimal).
Cool Manipulated Variable (Cool MV)
9107 2393 25491 6393 X X 1
Same as RAM address 14421
(decimal).
Motor opening feedback value (MFB)
9108 2394 25492 6394 X X 1
Same as RAM address 14417
(decimal).
AT progress
9109 2395 25493 6395 X X —
Current transformer (CT) current
value 1
9110 2396 25494 6396 X X 1
Same as RAM address 14418
(decimal).
Current transformer (CT) current
value 2
9111 2397 25495 6397 X X 1
Same as RAM address 14419
(decimal).
Timer remaining time 1
9112 2398 25496 6398 X X S
Timer remaining time 2
9113 2399 25497 6399 X X S
Timer remaining time 3
9114 239A 25498 639A X X S
Timer remaining time 4
9115 239B 25499 639B X X S
Timer remaining time 5
9116 239C 25500 639C X X S
Timer remaining time 6
9117 239D 25501 639D X X S
Timer remaining time 7
9118 239E 25502 639E X X S
Timer remaining time 8
9119 239F 25503 639F X X S
STEP operation No.
9120 23A0 25504 63A0 X X S
STEP operation remaining time
9121 23A1 25505 63A1 X X S
STEP operation remaining time (sec.)
9122 23A2 25506 63A2 X X S
LSP value in use
9123 23A3 25507 63A3 P
Same as RAM address 14593
(decimal). (Note 3)
PV before ratio, bias, and filter
9124 23A4 25508 63A4 X X P
RSP before ratio, bias, and filter
9125 23A5 25509 63A5 X X P
Status
Input alarm status
9201 23F1 25585 63F1 X X —
Bit 0:
AL0
1
(PV over-range)
Bit 1:
AL02
(PV under-range)
Bit 2:
AL03
(CJ, RTD burnout)
Bit 3: Undefined.
Bit 4:
AL05
(RSP over-range)
Bit 5:
AL06
(RSP under-range)
Bit 6:
AL07
(MFB burnout)
Bit 7 to 8: Undefined.
Bit 9:
AL
10
(Motor adjustment
failure)
Bit 10:
AL
1
1
(CT over-range)
Bit 11 to 15: Undefined.
(Note 3) If the value is read immediately after it has been written into the SP or the LSP in use, the value still may
not be changed. The value is updated after the cycle time has elapsed.
(Note 4) If the SP or the LSP in use is read immediately after the value has been written into the LSP group
selection, the value still may not be changed. The value is updated after the cycle time has elapsed.
(Continue on next page.)