EasyManuals Logo

Baldor NextMove ESB-2 User Manual

Baldor NextMove ESB-2
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #66 background imageLoading...
Page #66 background image
MN1957 Operation 5-21
www.baldormotion.com
5.7.2 Underdamped response
If the graph shows that the response is underdamped (it overshoots the demand, as shown
in Figure 35) then the value for KDERIV should be increased to add extra damping to the
move. If the overshoot is excessive or oscillation has occurred, it may be necessary to
reduce the value of KPROP.
Figure 35: Underdamped response
9. Click in the KDERIV and/or KPROP boxes
and make the required changes. The ideal
response is shown in section 5.7.4.
Measured position
Demand position
Servo Systems Co. • 115 Main Road • P.O. Box 97 • Montville, NJ,
07045-0097 • (973) 335-1007 • Toll Free: (800) 922-1103
Fax: (973) 335-1661 • www.servosystems.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baldor NextMove ESB-2 and is the answer not in the manual?

Baldor NextMove ESB-2 Specifications

General IconGeneral
BrandBaldor
ModelNextMove ESB-2
CategoryController
LanguageEnglish

Related product manuals