information. Information about usage of the Barionet analog registers and
converting the register values you can find in chapter 4.
2.3 How to use / wire a relay ?
The Barionet 50/100 relays (and the digital outputs) know two states (ON or
OFF). It´s the prefered choice for switching (on/off) connected devices.
Make sure the equipment connected to the relay never overloads a relay
(also not with the peak load when turning on) otherwise it can destroy the
relay!
Barionet50 relay supports max 0.5A at 30VDC (15W peak).
Barionet100 relay supports max 5A at 240VAC (1200 Wp).
Another difference between Barionet 50 and 100 relays is the Barionet100
relay has 3 pins (Common, NO and NC). NO means normally open and
closes by switching, NC means it´s normally closed and opens by switching.
By selecting which pin you use you decide for the desired behavior. The
Barionet50 has only 2 pins (Common and NO).
BARIX AG | 17. Oct. 2013 | Barionet Hands-on Training Guide | Page 11/38