To read state information add a request for “Read Coil status”. The offset 1
means it will start with Modbus/Barionet register 1 and the length 4 defines
the number registers to read (inclusive start register).
To write/set a Modbus/Barionet register add a “Write” for “05 Force Single
Coil”. The offset 2 means it writes to register 2 the defined value (1). In this
case it will activate the second Barionet relay.
BARIX AG | 17. Oct. 2013 | Barionet Hands-on Training Guide | Page 34/38