(i)Thebasicdesignparametersforthecircuitare:
I
b>
I
gwhere
I
bisthedesigncurrentandIgistheratedoutputcurrentoftheEcogen
I
n>
I
bwhereInisthenominalcurrentoftheoverloadprotectivedevice
DisconnectionofthefinalcircuitintheeventofanearthfaultonthecircuitanddeenergisingoftheEcogenshouldbothoccurwithinanoverallmaximumtimeof
0.4sforTNsystemsand0.2sforTTsystems.However,iftheprotectivedeviceforautomaticdisconnectionincaseofanearthfaultdisconnectslineandneutral
conductors,itisnotnecessarytotakeaccountofthetimetakenfortheEcogentodeenergise.
(ii)WhereanEcogenisconnectedonthesamesideofanRCDasfinalcircuitsprotectedbythatRCD,theRCDmustdisconnectthelineandneutralconductors.
(iii)TheEcogenmustbeprovidedwithmeansofisolationandofswitchingoffformechanicalmaintenance.
16.ConnectionofaEcogentoanexistingfinalcircuit
(i)Thebasicdesignparametersforthecircuitare:
I
z>
I
n+
I
gwhere
I
zisthecurrentcarryingcapacityoftheconductorsofthefinalcircuit,Inisthenominalcurrentoftheoverloadprotectivedeviceand
I
gistherated
outputcurrentoftheEcogen.Thismayrequiretheprotectivedevicetobereplacedwithonehavingalowernominalcurrentrating.
DisconnectionofthefinalcircuitintheeventofanearthfaultonthecircuitanddeenergisingoftheEcogenshouldbothoccurwithinanoverallmaximumtimeof
0.4sforTNsystemsand0.2sforTTsystems.However,iftheprotectivedeviceforautomaticdisconnectionincaseofanearthfaultdisconnectslineandneutral
conductors,itisnotnecessarytotakeaccountofthetimetakenfortheEcogentodeenergise.
IMPORTANT:IndesigningaconnectionfortheEcogen24/1.0theelectricalinstaller
hastoconsideralltheissuesthatwouldneedtobecoveredforaconventionalfinal
circuit,including:
InAccordancewithBS:7671.
themaximumdemand(andthegeneratoroutput)
thetypeofearthingarrangement
thenatureofthesupply
externalinfluences
compatibility,maintainabilityandaccessibility
protectionagainstelectricshock
protectionagainstthermaleffects
protectionagainstovercurrent
isolationandswitching
equipmentselectionandinstallationissues
Theelectricalinstallershouldcheckthattheprospectivefaultcurrentwouldnot
changesufficientlytoexceedthefaultratingofexistingprotectivedevices.
Fig.13
Fig.13a

Other manuals for Baxi ECOGEN 24/1.0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baxi ECOGEN 24/1.0 and is the answer not in the manual?

Baxi ECOGEN 24/1.0 Specifications

General IconGeneral
BrandBaxi
ModelECOGEN 24/1.0
CategoryBoiler
LanguageEnglish

Related product manuals