ISTRUCTIONS PERTAINING TO THE INSTALLER
12. MAKING THE ELECTRICAL CONNECTIONS
Electrical safety of the appliance is only guaranteed by correct grounding, in accordance with the rules in force.
Connect the boiler to a 230V monophase + ground power supply by means of the three-pin cable supplied
with it and make sure you connect polarities correctly.
Use a double-pole switch with a contact separation of at least 3mm in both poles.
In case you replace the power supply cable t a HAR H05 VV-F’ 3x0.75mm
2
cable with an 8mm diameter max.
IMPORTANT: Check that the overall current drawn by accessories connected to the appliance is less
than 2 A. If the value is greater, a relay must be wired between the boiler control circuit board and the
accessories drawing the higher current.
12.1 TERMINAL BLOCKS ACCESS
• Cutoffpowertotheboilerwiththetwo-poleswitch.
• Removethetopfaciapanelcover(whichisheldbymagnets).
• Unscrewthetwoscrewsholdingthefaciapanelinplace.
• Swingthefaciapanelforwards.
Main terminal block M1
• Removetheclip-oncoverfromterminalstripM1.
• Themainterminalblockincorporatesafastblow3.15Afuse(gure8).Removetheblackfuseholderto
check and/or replace the fuse.
Terminal block M2
• UnscrewthexingscrewandremovethecoverfromterminalblockM2.
Terminal block M3
• Unscrewthexingscrewsandremovethemaincover.
Figure 8
Terminal board
Terminal board
Cover
Terminal board
Cover
0902_1201 / CT_0674
CAUTION
If the appliance is directly connected to a underoor system, install a safety thermostat to prevent the latter from overheating.