Page 1-42 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Specifications
Chapter 1: Introduction
Table 1-12. Cabling Requirements from the Master Alarm Module to the
Source Equipment
Table 1-13. Network Communication Cable
Table 1-14. Audible Specifications
Table 1-15. Environmental Specifications
Environmental Specification Dimensions
Operating temperature 50°F to 120°F (10°C to 49°C)
Storage temperature - 40°F to 185°F (- 40°C to 85°C)
Operating humidity 0% to 85% non-condensing
Storage humidity 0% to 85% non-condensing
FCC Part 15 Class A, emissions
Audible Specifications Dimensions
Area Alarm audible output 80 dBA at one meter minimum
Master Alarm audible output 80 dBA at one meter minimum
Local Alarm audible output 80 dBA at one meter minimum
Specifications Dimensions
Master Alarm to alarm network devices Standard Ethernet 10BaseT cable
Network Communications Board to alarm
network devices
Standard Ethernet 10BaseT cable
Specifications Dimensions
Distance Maximum 10,000' (3048 m)
Cable Stranded, 22-gauge, shielded, twisted pair
Signal Power 20 V DC, 20 mA maximum