EasyManuals Logo

Bender ISOMETER isoEV425 User Manual

Bender ISOMETER isoEV425
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
Modbus register assignment of the ISOMETE
46
isoEV425_D00126_09_M_XXEN/03.2019
3012 RW
Memory function
for alarm mes-
sages
(Fault memory)
"M"
UINT 16 ---
0 = Inactive
1 = Active
3013 RW
Operating mode
of relay 1 "r1"
UINT 16 ---
0 = n.o.
1 = n.c.
3014 RW
Operating mode
of relay 2 "r2"
UINT 16 ---
0 = n.o.
1 = n.c.
3015 RW Bus address "Adr" UINT 16 --- 0 / 3 … 90
3016 RW Baud rate "Adr 1" UINT 16 ---
0 = BMS
1 = 1.2 k
2 = 2.4 k
3 = 4.8 k
4 = 9.6 k
5 = 19.2 k
6 = 38.4 k
7 = 57.6 k
8 = 115.2 k
3017 RW Parity "Adr 2" UINT 16 ---
0 = 8N1
1 = 8O1
2 = 8E1
3 = 8N2
3018 RW
Start-up delay "t"
during device
start
UINT 16 s 0 …10
3019
RW Response delay
"ton" for relays K1
and K2
UINT 16 s 0 … 99
Register
Property Description Format
Unit
Value range