Technical data
61
isoPV425_D00028_09_M_XXEN/05.2018
Classification of mechanical conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) .............................................................................................................................. 3M4
Transport (IEC 60721-3-2) ..................................................................................................................................... 2M2
Long-term storage (IEC 60721-3-1) ...................................................................................................................... 1M3
Connection
Connection type screw-type terminal or push-wire terminal
Screw-type terminals:
Nominal current.....................................................................................................................................................≤10 A
Tightening torque...............................................................................................................0.5…0.6 Nm (5…7 lb-in)
Conductor sizes.............................................................................................................................................AWG 24-12
Stripping length ......................................................................................................................................................8 mm
Rigid/flexible........................................................................................................................................... 0.2…2.5 mm
2
Flexible with ferrules with/without plastic sleeve .............................................................................. 0.25…2.5 mm
2
Multi-conductor rigid............................................................................................................................ 0.2…1.5 mm
2
Multi-conductor flexible.........................................................................................................................0.2…1.5 mm
2
Multi-conductor flexible with ferrules without plastic sleeve ............................................................0.25…1.5 mm
2
Multi-conductor flexible with TWIN ferrules with plastic sleeve........................................................0.25…1.5 mm
2
Push-wire terminals:
Nominal current.....................................................................................................................................................≤10 A
Conductor sizes.............................................................................................................................................AWG 24-14
Stripping length ....................................................................................................................................................10 mm
rigid ......................................................................................................................................................... 0.2…2.5 mm
2
flexible without ferrules........................................................................................................................ 0.75…2.5 mm
2
flexible with ferrules with/without plastic sleeve............................................................................... 0.25…2.5 mm
2
Multi-conductor flexible with TWIN ferrules with plastic sleeve..........................................................0.5…1.5 mm
2
Opening force ........................................................................................................................................................... 50 N
Test opening, diameter ................................................................................................................................. 2.1 mm
Wiring of the terminals Up, AK1, GND, AK2 ......... refer to technical data AGH420 under the heading "Connection"
Other
Operating mode ........................................................................................................................... continuous operation
Mounting ..................................................................................................... cooling slots must be ventilated vertically
Degree of protection, built-in components (DIN EN 60529) ................................................................................. IP30
Degree of protection, terminals (DIN EN 60529) .................................................................................................... IP20