3. Function
3.1 Device characteristics
Monitoring for unearthed AC and DC systems with galvanically con-
nected rectifiers or inverters
Measurement of the nominal system voltage U
n
(True RMS) with und-
ervoltage and overvoltage detection
Measurement of residual voltages system to earth (L+/PE and L-/PE)
Automatic adaptation to the system leakage capacitance C
e
up to
1000 µF
Automatic device self-test with connection monitoring
Selectable start-up delay, response delay and delay on release
Two separately adjustable response value ranges of 1kΩ …500 kΩ
(Alarm 1, Alarm 2)
Alarm signalling via LEDs („AL1“, „AL2“), a display and alarm relays
(„K1“, „K2“)
N/C operation or N/O operation of the relays selectable
Measured value indication via multi-functional LCD
Fault memory can be activated
RS-485 (galvanically isolated) including the following protocols:
– BMS interface (Bender measuring device interface) for data
exchange with other Bender components
– Modbus RTU
– IsoData (for continuous data output)
Password protection to prevent unauthorised parameter changes