30
Bentone B 30/B 40 J/K
5. Pump instructions
5.1 Suntec AS47CK
5.1.1 Technical data
Viscosity range: 1,0–12,0 mm
2
/s
Pressure range: 7–12 bar
Oil temperature: max. 60°C
5.1.2 Components
1. Solenoid valve
2. Nozzle connection G 1/8”
3. Vacuum manometer connection G 1/8”
4. Manometer connection G 1/8”
5. Filter
6. Suction line G 1/4”
7. Metal plug G 1/4”
8. Return plug
9. Return line G 1/4”
10. Pressure regulation
5.1.3 Filter replacement
Cut off the power and shut off the oil.
Remove the pump cover with the aid
of a 4 mm Allen key. If necessary a
screwdriver may be used between the
cover and the housing to carefully pry
the cover loose. Replace the old filter by
a new one. Replace the cover, tighten
lightly.
Do not forget to replace the gasket.
Open the oil supply and switch on the
power.
5.1.4 One-pipe system
Conversion to one-pipe system
Remove the return plug (8), plug the return
line (9) with the metal plug (7) G 1/4”.
5.1.5 Two-pipe system
Conversion to two-pipe system
Remove the metal plug (7) G ¼”, fit the return plug (8) in the return line (9).
Return plug are not included in products with one-pipe system, separately
sold.