burner permitted. Commissioning is to be carried out by qualifi ed
professionals only.
Prior to commissioning, the following points should be checked:
- all fi tting and installation work has been completed and approved
- the electrical installation has been carried out properly, the correct
fuses added to circuits and measures to safeguard enclosures on
electrical devices and all wiring have been checked
- ue gas ducts and combustion air ducts are not blocked
- all actuators and control and safety devices are in working order and
set correctly
Service
Service should be performed after 3,000 working hours, but no less
than once a year.
Only authorised personnel should perform the service.
Before servicing, shut off the fuel supply, switch off the installation’s
main switch and ensure accidental reconnection cannot take place.
Be careful: certain parts exposed after separation of the burner can be
hotter than 60°C.
Care should be taken by the installer to ensure that no electrical
cables or gas pipelines are crushed or damaged during installation or
servicing.
Only spare parts recommended by Enertech should be used.
All oil line components shall be assembled and mounted without
bending, torque and other mechanical or thermal stress.
Component “Useful life Recomended replacement” “Useful life Operation cykles”
Control system 10 Years 250 000
Valve proving system 10 Years 250 000
Pressure switch 10 Years 250 000
Flame guard 10 Years 250 000
Uv fl ame detector 10 000 h N/A
Stepper motor 500 000
Contaktor 10 Years 500 000
Service Service Service
Burner 1 Year 3000h
Filter 1 Year change 3000h Change
Oilhose 1 year control/change
Nozzle 1 year change 3000h Change
Electrods 1 Year Change /cleaning 3000h Change /cleaning
Brake plate 1 Year Change /cleaning 3000h Change /cleaning
Motor 1 Year 3000h
Cuppling chaft 1 year control/change 3000h control/change
Fan wheel “1 Year Change when dirty /unbalance” “3000h Change when dirty /unbalance”
Burner/Components must be recycled prior to local regulations.
171 90523-1 2016-10-02