9.4.23 Remote commands with addressing
If the RS485 communication interface has been selected, the number of
the instrument interrogated must be added to the remote commands
described in par. 9.4 on page 1-69.
The system comprises one Master terminal (e.g. a PC) and a number of
Slave terminals (e.g. weighing terminals).
Each weighing terminal is identified by a unique "terminal number".
In this way you can create a network of weighing terminals that can be
interrogated by the Master terminal.
The syntax of the remote commands has to be modified by the addition
of the two characters of the terminal number.
For example, the gross weight transmission command XB <CR>
becomes XB 01 <CR> to indicate that the request from the Master
terminal is addressed to the terminal number 01.