EasyManua.ls Logo

Bosch ACS 653-P - Input Test; Calibrate Air Flow (for R1234 Yf Only); ISV Purge Condition

Bosch ACS 653-P
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACS 653, ACS 663 Service Manual
SP00D00624 2021-04-08 Robert Bosch GmbH
40
Diagnostics and Testing

The input test displays the current state of
the measurable parts of the unit such as the
amount of refrigerant, temperatures, and the
various pressures present within the unit. The
values shown are absolute and indicate what is
happening within the unit at any given moment
during operation. The values are observable
only and cannot be changed or deleted. They
can indicate whether a sensor or device is
operating within the required limits for proper
unit operation.
1. From the Service Menu, scroll to .
2. Select  icon. The following displays:
Placeholders X and Y represent numbers
displayed during this test. A list of the sensors and
devices and what the values represent follows:






ISV Weight X.XXXYY ISV Weight
Drain Weight X.XXXYY Drain Weight
LS Press X.XYYY Low-Side Pressure
AC Press X.XYYY Accumulator
Pressure
ISV Press X.XYYY ISV Pressure
ISV Temp X.X
0
Y ISV Temperature
HP Sw X High-Pressure Switch
Overll X ISV Liquid Quantity
Air Flow XXXXrpm Fan Air Flow
(for R1234yf only)
3. Scroll through the sensors or devices to
observe their values. When nished, select
 icon to return to the Service Menu.

The air ow inside the unit must be present at
the correct volume to make sure enough air is
present to prevent the buildup of refrigerant and
to keep the compressor temperature below its
upper limit.
1. From the Service Menu, scroll to 
.
2. Select  icon. The following displays:
3. Check :
All body panels are installed.
Fan is clean and running.
4. Select  icon, and wait unit is performing
calibration automatically.
5. If calibration succeeds, unit will return to
service menu.
6. If calibration fails, unit will prompt user to
retry.

Displays internal storage vessel (ISV) pressure
and temperature.
1. From the Service Menu, scroll to 
.
2. Select  icon. The following displays:
3. Scroll to the  and
keep (I/0) pressed to purge
incondensable gas from tank.

Table of Contents

Related product manuals