EasyManua.ls Logo

Bosch ACS 653-P - Page 64

Bosch ACS 653-P
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACS 653, ACS 663 Service Manual
SP00D00624 2021-04-08 Robert Bosch GmbH
64
Diagnostics and Testing
  

Refrigerant Identication Identier Unstable Reading
Error 3
Possible reason:
1. Radio transmitters and arc welders.
Refrigerant Identication Identier Air Calibration Error Possible reasons:
1. Sampling path problem:
Brass lter clogged and/or sample
hose clogged.
Sample hose is broken, cracked
or punctured.
Sample hose is disconnected.
2. Identier internal piping problem:
One or more tubes are discon-
nected.
One or more tubes are broken,
cracked or punctured.
One or more tubes are clogged.
3. Identier white paper lter defective:
White paper lter is broken.
White paper lter is clogged.
White paper lter is disconnected.
4. Identier air intake or air exhaust
clogged.
5. Identier solenoid leaking during
calibration.
Refrigerant Identication Identier Refrigerant Flow
Error
Possible reasons:
1. Sampling path problem:
Brass lter clogged and/or sample
hose clogged.
Sample hose is broken, cracked
or punctured.
Sample hose is disconnected.
2. Identier internal piping problem:
One or more tubes are discon-
nected.
One or more tubes are broken,
cracked or punctured.
One or more tubes are clogged.
3. Identier white paper lter defective:
White paper lter is broken.
White paper lter is clogged.
White paper lter is disconnected.
4. Identifier solenoid issue during
analysis:
Identier solenoid is clogged.
Identier solenoid cable is defective.
Identier solenoid power board
issue.

Table of Contents

Related product manuals