SystemModules
FlexibleAutomation
4−41
Slot With the exception of expansion units in distributed expansion, the IE
module (interrupt mode) can be installed in any slot that accepts periph
eral modules.
.Note,
A detailed description of the module is given in Technical Description" P.−No. 3913.
Specifications External Supply Voltage 24V DC to DIN 19240
External Current Consumption max. 100mA
Internal Current Consumption
at 12V max. 30mA
Voltage Range/Current Range
Signal Range 0" −3V ... +5V
0 ... 2.5mA
Signal Range 1" +13V ... +30.2V
5.5 ... 13.5mA
Number of Inputs 16
8 are switchable in interrupt
mode
Switching Delay ON" 10 ms typical
Switching Delay OFF" 20ms typical
Simultaneity Factor 100%
Width 1 module width
Dimensions Dual Eurocard format
.Note,
Shielded cable should be used for signal lines.
Ordering Information Order No.
Interruptable Input Module IE 24V 050564