Page 82 P/N: 4998152533-02 Copyright 2007 Bosch Security Systems, Inc. DS7200V2-UK Installer's Guide
PART IV: CONTROL PANEL PROGRAMMING
Swinger Count for Alarm Output
Address: 1029
Default: 3
Selections:
0 (Swinger disabled)
1-15
Each individual zone has a swinger count for alarm output.
Swinger Shunt reports are not sent for Swinger Shunt for Alarm Output. Swinger Shunt reports have their own swinger count
(see
Swinger Count for Zone Reports on page 82). The Swinger Count is reset on both arming and disarming of the system,
allowing Swinger Shunt to work for both non-24-hour and 24-hour zones. A trouble condition occurs after Swinger Shunt.
Example: Assume the Swinger Shunt option is enabled, the control panel is armed, no zones are in alarm and the Swinger
Count for Alarm Output is set to 2. Zones 1, 3 and 5 go into alarm. At the end of Bell Time, the Swinger Count for Alarm
Output for Zones 1,3 and 5 decrements from 2 to 1. Since the counter does not reach zero, no zones are bypassed. A second
alarm event for any of those zones bypasses that zone.
When the Swinger Count is set to zero (0), Swinger Count for Alarm Outputs is disabled. The alarm
outputs activate on every new alarm.
Swinger Count for Zone Reports
Address: 1030
Default: 0
Selections:
0 (Swinger disabled)
1-15
This parameter sets the swinger count for zone alarm, trouble, and restoral reports. Swinger shut down for the control panel is
a global function that affects all zones. Swinger Shunt {33} reports are sent for Swinger Shunt of zones.
The Swinger Count is reset on both arming and disarming, allowing Swinger Shunt to work for both non-24-hour and 24-hour
zones.
Example: Assume the Swinger Shunt option is enabled, the control panel is armed and there are no alarms. When the zone
sends an Alarm or Trouble event to the control panel, the swinger count for zone reports is checked. If the counter is at zero,
the zone is already Swinger Shunted and no report is sent. If the counter is not at zero, the control panel decrements the
counter. If the counter then goes to zero after the report is sent, the Swinger Shunt {33} report is sent. The zone is then
swinger shunted. If the swinger count is set to zero (0), Swinger Count for Zone Reports is disabled. The control panel sends
all alarm or trouble events.
Bypass, Swinger Shunt, Sensor Trouble Report Options
Address: 1031
Default: 0
Selections: 0-15
Enter This Data Digit to Select Options
Bypass, Swinger Shunt, Sensor Trouble Report Options 0 1 2 3 4 5 6 7 8 9 10
11
12
13
14
15
No Options Selected
Zone Bypass and Swinger Shunt Reports Enabled
Bypass and Swinger Shunt Restoral Reports Enabled
Sensor Trouble Reports Enabled
Sensor Trouble Restoral Reports Enabled
This is a global parameter that affects all areas.
Use this parameter to enable Zone Bypass, Swinger Shunt and Sensor reports (and their respective restoral reports are
enabled).