DS7200V2-UK Installer's Guide Copyright 2007 Bosch Security Systems, Inc. P/N: 4998152533-02 Page 91
PART IV: CONTROL PANEL PROGRAMMING
Digit
1
Digit
2
Function Type Description
8 0 Follow PIN 32
8 1 Sked Only
This output type is only available for Outputs 1 to 15. Activated by Skeds. See Skeds on page 95 for more
information.
8 2 Change Outputs Activated/deactivated by Change Outputs function ([#][5][4]).
8 3 Always On Output is always activated.
8 4 Confirmed Alarm
Activates when the requirements for a confirmed alarm are met. Resets when the confirmed alarm is reset
by the installer.
8 5 Unconfirmed Alarm
Activates on any non-24-hr alarm, 24-hr tamper, 24-hr emergency, or 24-hr burglary alarm. Resets when
the confirmation alarm timer resets or when a PIN is entered.
8 6 Tamper
Activates on any tamper condition. Resets when tamper condition is restored and when Installer PIN is
entered and [System Reset] key is pressed.
8 7 Bypass Activates when any input is bypassed. Resets when all input bypasses are cleared.
8 8 Enhanced Siren
Activates on Exit Delay, Entry Delay, Chime, Alarm, Tamper, Trouble, or Bad Set. Resets at the end of
bell time or when a PIN is entered.
8 9 Alarm Abort Activates on a cancelled alarm. Resets when alarm is cleared.
8 10 RF Transmitter Missing Activates when any RF transmitter is missing.
8 11
RF Transmitter Low
Battery
Activates when any RF transmitter is reporting a low battery. For zone transmitters, the output activates
after the low battery is present for 100 hours.
8 12 RF Receiver Jamming Activates when RF Jamming is present for 5 minutes.
8 13 Fire Alarm Only Activates on Fire Alarm only. PIN resets. Does not pulse in Temporal Code 3 format.
8 14 Personal Alarm
Activates when one of its assigned areas is set to Personal Alarm. Resets by entering a valid user PIN,
pressing the [System Reset] key, or by RPS (system reset command). Activates on any of the following
conditions: (1) If a Duress User PIN is entered (2) If an Emergency key is active in an area and “Activate
Panic Alarm Response” and “Alarm Output” are enabled for the key (3) If a RF keyfob reports a Panic
alarm, or (4) If a zone configured for 24-hr Visible Panic (Zone Function Type 6) goes into alarm.
8 15 Q Button
Output activates when the [Q] button is pressed on a RF keyfob. For Steady or Pulse modes, [System
Reset] resets. This output function type is event-driven. See Mode (Steady, Pulse, One Shot), Output ##
on page 92 for more information. See the DS7200V2 Expert Programming Guide (P/N: 4998153891) for
more information on [Q] button programming.
Table 32: Output Function Types (continued)