Aspirating Smoke Detector Commissioning | en 109
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
Notice!
Once any faults have been rectified, the parameter settings must be restored to their original
status via the RPS software.
The commissioning procedure must be repeated from Calibrating the Airflow Sensor, page 104.
Once commissioning has been concluded, the set values must be collected and saved using
the DIAG Diagnostic Software. A printout of the set values should be placed in the project
folder.
See also
– Preparation, page 103
– Calibrating the Airflow Sensor, page 104