Aspirating Smoke Detector Appendix | en 125
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
Number of openings
Pipe
shape
U
Fans
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 20 21 22 24 32
M 6.9 80 80 80 80 80 80 70 70 70
≥9 12
0
12
0
12
0
12
0
12
0
12
0
12
0
12
0
12
0
Double U 6.9 80 80 80 80 80 80 80 80
≥9 10
0
10
0
10
0
10
0
10
0
10
0
10
0
10
0
9.3 Planning with air filter
M = module S = sensitivity (% LT/m) MA = main alarm PA = pre-alarm
Number of openings
D
M-
S 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 20 21 22 24 32
01
(0
5)
0.015
(0.05)
M
A
A A A A A A A A A A A A A A A A A A A A A A
0.03 (0.1) M
A
A A A A A A A A A A A A A A A A A A B B B B
0.06 (0.2) M
A
A A A A A A A A A A B B B B B B B B B B B C
0.12 (0.4) M
A
A A A A A B B B B B B B B C C C C C C C C
10
(2
5)
0.1 (0.25) M
A
A A A A A A A A B B B B B B B B B B C C C C
0.2 (0.5) M
A
A A A A B B B B B B C C C C C C C C
0.4 (1) M
A
A A B B B C C C C C
0.8 (2) M
A
A B C C C
50
(8
0)
0.313 (0.5) P
A
A A A A B B B B B B C C C C C C C C
0.5 (0.8) M
A
A A B B B B C C C C C C C
0.687 (1.1) P
A
A B B B C C C C C
1.0 (1.6) M
A
A B B C C C