Aspirating Smoke Detector Planning | en 45
Bosch Sicherheitssysteme GmbH Operation Guide 2018.04 | 2.0 | F.01U.130.926
U-pipe system for space protection
1 pipe system
FAS‑420‑TP1
FAS‑420‑TT1
2 pipe systems
FAS‑420‑TP2
FAS‑420‑TT2
FAS / FCS
FAS / FCS
A B C D I J
A B C D I J
U-pipe system for space protection
Limiting values Min. distance: FCS-320 – T-fitting 4m
U-pipe system Max. distance: FCS-320 – T-fitting 20 m
Max. branch length
With low fan voltage
With high fan voltage
50m
65m
Max. overall pipe length per pipe system (Ø 25mm)
With low fan voltage
With high fan voltage
120m
150m
Min. distance between 2 air sampling openings 4m
Max. distance between 2 air sampling openings 12m
Max. number of air sampling openings (n) per pipe system 20
U-pipe system Air sampling
opening
Number of air sampling openings
2 4 6 8 10 12 14 16 18 20
air sampling
opening in mm
a
A 5.2 3.6 3.4 3.0 2.5 2.5 2.0 2.0 2.0 2.0
B 4.4 3.4 3.0 3.0 2.5 2.0 2.0 2.0 2.0
C 3.6 3.2 3.0 2.5 2.5 2.0 2.0 2.0
D 3.4 3.2 3.0 2.5 2.5 2.0 2.0
E 3.2 3.0 3.0 2.5 2.5 2.0
F 3.4 3.2 3.0 2.5 2.5
G 3.6 3.4 3.0 2.5
H 3.6 3.4 2.5
I 3.6 3.6
J 3.8