54 en | Planning Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
Double U-pipe system - single-hole monitoring
1 pipe system
FCS-320-TP1
FCS-320-TT1
2 pipe systems
FCS-320-TP2
FCS-320-TT2
FAS / FCS
FAS / FCS
C
C
B
B
A
A
Double U-pipe system for space protection
Limiting values Min. distance FCS-320– last T-fitting 4m
Double U-pipe Max. distance FCS-320 – last T-fitting 20m
Max. branch length
With low fan voltage
With high fan voltage
20m
30m
Max. overall pipe length per pipe system (Ø 25mm)
With low fan voltage
With high fan voltage
100m
140m
Min. distance between 2 air sampling openings 4m
Max. distance between 2 air sampling openings 12m
Max. number of air sampling openings (n) per pipe system 12
Double U-pipe Air sampling opening Number of air sampling openings
4 8 12
Ø air sampling
opening in mm
a
A 4.0 3.0 2.5
B - 3.4 3.0
C - - 3.0
a
Punch diameter of the aspiration reducing film sheet
Double U-pipe system activation thresholds per pipe system
Activation
thresholds
Number of openings 4 8 12
1 obstructed opening I
2 obstructed openings II I
3 obstructed openings 0 II I