88 en | Installing the Aspirating Smoke Detector Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926 Operation Guide Bosch Sicherheitssysteme GmbH
Sensitivity DIP settings
DM-TP-01(05)
DM-TT-01(05)
DM-TP10(25)
DM-TT-10(25)
DM-TP50(80)
DM-TT-50(80)
Switch 1 Switch 2
0.12%/m
(0.4%/m)
0.8%/m
(2%/m)
- on on
0.06%/m
(0.2%/m)
0.4%/m
(1%/m)
- off on
0.03%/m
(0.1%/m)
0.2%/m
(0.5%/m)
1.0%/m
(1.6%/m)
on off
0.015%/m
(0.05%/m)
0.1%/m
(0.25%/m)
0.5%/m
(0.8%/m)
off off
Alarm delay DIP settings
Switch 3 Switch 4
0 seconds off off
10 seconds on off
30 seconds off on
60 seconds on on
Activation threshold for airflow malfunction DIP settings
Switch 5 Switch 6
Low (+/- 10% volume flow change) on off
Average (+/- 20% volume flow change) off on
High (+/- 30% volume flow change) off off
Very high (+/- 50% volume flow change) on on
Airflow fault delay DIP settings
Switch 7 Switch 8
30 seconds off on
2 minutes on off
15 minutes on on
60 minutes off off
Trouble logging DIP settings LOGIC·SENS filter DIP settings
Switch 9 Switch 10
not saving off off off
saving on on on