26 en | Installation MAP 5000
2016.06 | 17 | F.01U.168.332 Installation manual Bosch Sicherheitssysteme GmbH
Installing the 12 V converter
2.9 Installing the fuse plate (SIV)
1. Mount the fuse plate (SIV) onto the accessory mounting plate as shown in the figure
below (screws not supplied).
2. Connect the field wiring to the terminal block of the fuse plate (SIV) as shown in the
figure below and leave the other ends unconnected.
Notice!
Use the corresponding ratings for the fuses SI 1 ... SI 5. (minimum 250 mA, maximum 1 A
depending on the connected loads).
The overall current of all SIV outputs must not exceed the available maximum current of the
voltage output used.