MAP 5000 Connections | en 47
Bosch Sicherheitssysteme GmbH Installation manual 2016.06 | 17 | F.01U.168.332
Shielded stub and loop wiring
For both stub and loop wiring, the following additional requirements apply for shielded wires:
– Usage of an additional shielding wire from the central unit
– Routing across the shortest possible distance to the earth terminal
– Looping the shield wire through the LSN elements
Other connections of the additional shielding wire at other locations are not permitted. With
loop wiring, the additional shielding wire must be connected at both loop ends.
LSN gateway loop configuration