Loading...
MAP 5000 Appendices | en 79
Bosch Sicherheitssysteme GmbH Installation manual 2016.06 | 17 | F.01U.168.332
AE 4 Access for manufacturers via RPS for MAP
1. Authorize the manufacturer user with an AE 2 user with corresponding permissions
(control center: main menu page 1 > maintenance page 3 > manufacturer permission).
2. Open control panel enclosure.
The internal warning device is activated for 3 sec.
1
3. Switch to installer mode = AE 3 (Installer button, page 67).
4. Login with the passcode of the manufacturer at the installer control center (Manufacturer
authorization, page 60).
5. Establish a connection between the panel and RPS.
1) Activation of the warning device on opening the control panel enclosure may be omitted if
access to access level 3 is controlled by switches, locks (at least 15,000 variation possibilities)
or other equivalent means.
Internal warning device when control panel enclosure is opened
An internal warning device must be provided that trips a time-limited audible alarm when the
control panel enclosure is opened in unarmed state.
1. Assign device siren to free output.
2. In the properties> behavior item list of the device siren, activate the option Include
External Tamper Alarm Disarmed of Onboard Tamper.
Functions of the access levels
The assignment of the functions to the access levels 2 and 3 can be adapted in RPS.
Further subdivisions are possible within the access levels if the owner wishes to grant the
users different permissions: User Manager > Permission Sets
General permissions Access level
1 2 3 4
May silence buzzer on control center X X
May change own user passcode X X X
May transmit/receive programming with RPS X
May receive history with RPS X
May perform diagnostics with RPS X
May perform software updates with RPS X X
Operations category permissions 1 2 3 4
May disable device X
May enable device X
May turn chime on/off X X
May change schedule X X
May edit blocking time X X
User category permissions 1 2 3 4
May add user X X
May delete user X X