2/10 Bosch Rexroth AG Hydraulics
Additional information RE 30110-Z/10.12
Configurations for VT-VSPA2-1-2X/V0/...
Factory setting
VT-VSPA2-1-2X/V0/...
VT 3026
(RE 30093)
VT 3000
1)
(RE 29935)
VT 3006
1)
(RE 29926)
VT 3013
(RE 29937)
VT 3017
(RE 29939)
VT 3014
(RE 29937)
VT 3018
(RE 29939)
VT-VSPA2-1-1X/T1
VT-VSPA2-1-1X/T5
(RE 30112)
VT-VSPA2-50-1X/T1
VT-VSPA2-50-1X/T5
(RE 30113)
Configuration
for:
A4VG…EP2
.WRZ
(to component
series 6X)
DBEP6, 3DREP6
(in each case
component
series 1X)
4WRA6 4WRA10
4WRA6
(from compo-
nent series 2X)
4WRA10
(from compo-
nent series 2X)
3DREP6
(from component
series 2X),
.WRZ
(from component
series 7X)
Inversion
J1
Not inverting
Jumper open
Jumper open Jumper open Jumper open Jumper open Jumper open Jumper open Jumper open
Ramp function
J2
Ramp on
Jumper open
Jumper open Jumper open Jumper open Jumper open Jumper open Jumper open Jumper open
Ramp time
J3
30 ms to 5 s
Jumper open
Jumper open Jumper open Jumper open Jumper open Jumper open Jumper open Jumper open
Step function
J4
Step function on
Jumper open
Jumper open Jumper open Jumper open Jumper open Jumper open Jumper open Jumper open
Clock frequency
J5, J6 closed
170 Hz
Setting by means
of potentiometer f
100 Hz ± 10 %
2)
170 Hz ± 10 % 190 Hz ± 10 %
2)
Jumper 6 open
100 Hz ± 10 %
2)
300 Hz ± 10 %
2)
180 Hz ± 10 %
2)
220 Hz ± 10 %
2)
Maximum current
setting
J7 closed
1500 mA
Setting by means
of Gw+ and Gw–
600 mA
2)
800 mA
2)
1500 mA 1500 mA 2500 mA
2)
2500 mA
2)
1500 mA
Step level
J8, J9 closed
500 mA
Setting by means
of S+ and S–
200 mA
2)
200 mA
2)
500 mA 500 mA 350 mA
2)
350 mA
2)
500 mA
Table 1: Configurations VT-VSPA2-1-2X/V0/T1 and T5
1)
When using the amplifiers VT-VSPA2-1-2X/V0/... as replacement for the amplifier types VT 3000 and VT 3006, the supply voltage must lie between 28 and 30 VDC!
2)
These values must be set!
In all measurements, you must measure from the measuring socket "I" against "M0"!
For more information (characteristic curves, etc. …) refer to the data sheets specified above.
Please note:
The order of the following steps must imperatively be observed!