User manual WTS Ver.1.16
Seite 49 von 52
POSSIBLES COMMAND TO SEND TO THE COMMAND REGISTER (40006)
0
SEMI-AUTOMATIC TARE enabling
(net display)
SEMI-AUTOMATIC TARE disabling
(gross display)
Keypad and display unlock
TARE WEIGHT ZERO SETTING
for calibration
Save first sample weight for
calibration
Real calibration cancellation
Add sample weight for calibration
COMMUNICATION EXAMPLES
The numerical data below are expressed in hexadecimal notation with prefix h.
EXAMPLE 1
Command for multiple writing of registers (hexadecimal command 16, h10):
Assuming that we wish to write the value 0 to the register 40017 and the value 2000 to the
register 40018, the string to generate must be:
h01 h10 h00 h10 h00 h02 h04 h00 h00 h07 hD0 hF1 h0F
The instrument will respond with the string:
h01 h10 h00 h10 h00 h02 h40 h0D
Address of the first register H
Address of the first register H
Address of the first register L
Address of the first register L
Number of registers to send H
Number of registers to send L