Page 19 - Programming Manual 24805480/14-11-2012 319F92C ver. 1.2 -The data and information in this manual may be changed at any time with no obligation on BRAHMS’s part to notify anyone of this.
ENGLISH
GENERAL ALARM
[0..255] SEC 090
+
-
DELAY:NO NETWORK
[0..255] MIN 060
Missing network notification delay:
(Default:
060
)
S
A
It determines every how often the LACK of ELECTRIC POWER is considered an anomaly.
The NETWORK MISSING event is inserted in the events log. In case of power outages, the
breakdown LED indicator light will stay permanently on.
setting a time greater than 60 minutes voids the reference regulations.
+
-
General alarm time: (Default:
090
)
F
S
A
During the GENERAL ALARM TIME, the GENERAL ALARM RELAY is active.
The general alarm condition is determined by the inputs’ activations.
SABOTAGE
[0..255] SEC 090
+
-
Sabotage time: (Default:
090
)
F
S
A
Alarm time associated to inputs for 24 hours or to tamper /tampering.
TECHN. ALRM
[0..255] SEC 090
+
-
Technical alarm time: (Default:
090
)
F
S
A
Alarm time associated to technical-type inputs.
BURGL. ALARM
[0..255] SEC 000
+
-
Burglary alarm time: (Default:
000
)
F
S
A
Alarm time associated to burglary-type inputs.
BUZZER OUTPUT 01
[0..255] SEC 000
+
-
Exit time buzzer: (Default:
000
)
F
S
A
The BUZZER ALARM condition is determined by activations of inputs which have their
“Buzzer Output” properties set to ON.
OUTPUT TIME
[0..255] SEC 050
+
-
Exit time: (Default:
050
)
F
S
A
During the EXIT TIME the control unit checks the state of the inputs and warns about
any open ones. This notification takes place: visibly on keypads and inserter LEDs and
acoustically on the keypad buzzers.
ENTRANC1 TIME
[0..255] SEC 030
+
-
Entrance times 1 and 2: (Default 1:
030
) (Default 2:
040
)
F
S
A
When the system is inserted, an unbalanced input of the DELAYED 1 or 2 type triggers the
respective ENTRANCE TIME counter. During the ENTRANCE TIME, the control unit does not
trigger the alarm if any PATH or DELAYED-type inputs are unbalanced.
At the end of the ENTRANCE TIME, if the system is not DISINSERTED, a GENERAL ALARM
is triggered.
setting a time greater than 45 minutes voids the reference regulations.
ENTRANC2 TIME
[0..255] SEC 040
+
-