EasyManua.ls Logo

Brahms Proxinet 8

Default Icon
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 18 - Programming Manual 24805480/14-11-2012 319F92C ver. 1.2 -The data and information in this manual may be changed at any time with no obligation on BRAHMS’s part to notify anyone of this.
ENGLISH
SECURITY 001
NEGATIVE
Security: (Default:
NEGATIVE
)
S
A
NEGATIVE
The output is normally deactivated and is activated when it is
commanded.
Example: connecting a relay to an open collector output to SECURITY
NEGATIVE, the relay will be normally de-energised and will energise only
when the output is closed.
POSITIVE
The output is normally active and is deactivated when it is
commanded.
Example: connecting a relay to an open collector output to SECURITY
POSITIVE, the relay will be normally energised and will de-energise only
when the output is closed.
+
-
DESCRIPTION 001
OUTPUT 01
*
REM. ACTIV 001
NO
Remote activation: (Default:
NO
)
S
A
if activated (YES) it lets you remotely activate the output via voice guide or sms or
Example: we want to activate an impulsive-type output via SMS to send a start
command to heating.
Code 1: password
123456
; telecontrol
YES
.
Output 2: type
IMPULSIVE
; activating from remote
YES
.
Telephone options: telecontrol from SMS
YES
.
SMS to send: activate heating.CRSMS.123456.6002.
+
-
FOLLOWS OUTP. 001
NO
Output follows: (Default:
NO
)
S
A
For binding the activation status of one output as a function of another output.
Example: we want two outputs on the general alarm bus.
Output 10: type
STABLE
Output 21: type
STABLE
; follows output
OUTPUT 10
.
In the outputs Association menu, assign general alarm status of the areas
OUTPUT 10
.
+
-
Output description:
S
A
For editing the output description.
2.9 Times
TIMES 13
*
AUTOTEST INTERV.
[0..255] HRS 000
Autotest intervals:
(Default:
000
)
S
A
It determines every how many hours the control unit should automatically perform a
functional test. The first auto-test after switching on the control unit is done after the time
defined by AUTOTEST INTERVAL.
If the value is set to 000, the autotest is not performed.
Example: this function is generally employed by surveillance as system survival.
Telephone 15: security firm number; format
CONTACT-ID
; system code
XXXX
.
Autotest interval
24
hours.
In telephone notifications: telephones for autotest notifications
--------------#-
.
+
-
BATTER TEST INT.
[0..255] MIN 060
Battery test interval:
(Default:
060
)
S
A
It determines every how many minutes the control unit should automatically perform a
BATTERY DYNAMIC TEST. If the value is set to 0 the test is deactivated. In case the battery
is rundown, the breakdown led indicator light flashes and keeps flashing until the next
test; also, you can also either associate an output or a remote communication.
Note: the breakdown status remains active until the next “BATTERY TEST”. To remove the
breakdown status following battery replacement, perform a manual “BATTERY TEST” from
the technical menu.
+
-