© 2022 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS6100 Installation Manual
31
Brivo ACS6100 Installation Manual
NOTE: Refer to our Approved Reader Compatibility List and connection diagrams.
1. Use the wire recommended by the manufacturer of the reader or keypad. If no wire is recommended, use a
minimum of 22 AWG wire with sucient conductors that include shield (drain).
2. If your reader interface uses standard Wiegand conventions, connect the wire properly to the terminal
block on the appropriate board node. Following is a typical, but not universal, wiring guide. Refer to
our Approved Reader List for guidelines related to your specic reader or keypad.
a) Connect the green reader wire to the DATA0 terminal. This is the standard Data 0 circuit for
Wiegand readers.
b) Connect the white reader wire to the DATA1 terminal. This is the standard Data 1 circuit for
Wiegand readers.
c) Connect the black reader wire to the GND terminal. This is the standard Ground circuit for
the reader.
d) Connect the blue reader wire to the BUZZ terminal. This is the standard Buzzer circuit for the
reader.
e) Connect the red reader wire to the 12VDC terminal. This provides +12VDC to power the
reader.
f) Connect the orange reader wire to the GRN LED terminal. This is the green LED circuit.
g) Connect the brown reader wire to the RED LED terminal. This is the red LED circuit.
3. If your reader is OSDP using RS-485 wiring conventions, connect the wire properly to the terminal block on
the appropriate board node. Following is a typical, but not universal, wiring guide. Refer to our Approved
Wiegand and OSDP Reader List for guidelines related to your specic reader or keypad.
a) Connect the wire to the RXD+ terminal. This is the standard RXD+ circuit for OSDP readers
using RS-485.
b) Connect the wire to the RXD- terminal. This is the standard RXD- circuit for OSDP readers
using RS-485.
c) Connect the wire to the GND terminal. This is the standard Ground circuit for OSDP readers
using RS-485.
d) Connect the wire to the 12VDC terminal. This provides +12VDC to power OSDP readers using
RS-485.