EasyManuals Logo

Bryant 549J Series User Manual

Bryant 549J Series
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
29
Table 12 -- Menu Structure* (cont)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
[
EXPANDED P ARAMETER NAME
Notes
SETPOINTS
MAT SET 53_F
(12_C)
38 to 70_F;
(3 to 21_C)
increment by 1
SUPPLY AI R SETP OINT
Setpoi nt determines where the economizer will modulate the OA damper to
maintain the mixed air temperature.
SeeMenuNote2.
LOW T LOCK 32_F
(0_C)
---45 to 80_F;
(---43 to 27_C)
increment by 1
COMPRESSOR LOW TEMPERATURE LOCKOUT
Setpoi nt determines outdoor temperature when the mechanical cooling
canno t be turned on. Commonly referred to as the Comp ressor lock out. At
or below the set p o int the Y1---O and Y2---O will not be energ ized on the
cont ro lle r.
DRYBLB SET 63_F
(17_C)
48 to 80_F
(9 to 27_C)
increment by 1
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT
Setpoi nt determines where the economizer will assume outdoor air
temperature is good for free cooling; e.g.: at 63_F(17_C), unit will
economize at 62_F (16.7_C) and below and not economize at 64_F
(17.8_C) and above. There is a 2_F(1.1_C) deadband.
SeeMenuNote3
ENTH CURVE ES3 ES1, ES2, ES3, ES4, or
ES5
ENTHALPY CHANGEOVER CURVE
(Re q uires enthalpy sens o r opt ion)
Enthalp y bounda ry “curv e s for econom izing using si ngle enthalp y.
See pag e 36 for des c ription of entha lp y curve s.
DCV SET 1100ppm 500 to 2000 ppm;
increment by 100
DEMA N D CONTROLLED VENTILATION SETPO INT
Displays only if CO
2
se nsor is connec ted. Setp o int for Demand Controlled
Ventilation of space. Above the setpoint, the OA dampers will modulate
open to bring in additi onal OA to maintain a space ppm level below the
setpoint.
MIN POS 2.8 V 2to10Vdc
VENTILATION MINIMUM POSITION
Displays ONLY if a CO
2
se nsor is NOT co nnected .
Wit h 2 ---sp eed fan uni ts MIN POS L (low speed fan) and MIN POS H (hi gh
speed fan) setti ngs are required. Default for MIN POS L is 3.2V and MIN
POS H is 2.8V.
VENTMAX 2.8 V
2to10Vdc DCV MAXIMUM DAMPER POSITI ON
Displays only if a CO
2
se nsor is conne c ted. Used for Vbz (vent ilati o n max
cfm) setpoint. VENTMAX is the same setting as MIN POS would be if you
did not have the CO
2
sensor .
100 to 9990 cfm
increment by 10
IfOA,MARAandCO
2
se ns o rs are connec t e d and DCV CAL ENABLE is
set to A UTO mode, the OA dampers are controlled by CFM and di sp lays
from 100 to 9990 cfm.
2to10Vdc Wit h 2 ---speed fan units VENTMAX L (low speed fan) and VENTMAX H
(high speed fan) settings are required. Default for VENTMA X L is 3.2V and
VENTMAX H is 2.8V.
VENTMIN 2.25 V
2to10Vdc DCV MINIMUM DAMPER POSITION
Displays only if CO
2
sensor is connected. Used for Va (ventilation min cfm)
se t point . This is the ventilati o n requirement for less than maximum
oc c upancy of the space.
100 to 9990 cfm
increment by 10
IfOA,MARAandCO
2
se ns o rs are connec t e d and DCV CAL ENABLE is
set to A UTO mode, the OA dampers are controlled by CFM and di sp lays
from 100 to 9990 cfm.
2to10Vdc With 2--- speed fan units VENTMIN L (low speed fan) and VENTMIN H
(high speed fan) settings are required. Default for VENTMIN L is 2.5V
and VENTMIN H is 2.25V.
ERV OAT SP
[[
32_F
(0_C)
0to50_F;
(---18 to 10_C)
increment by 1
ENERGY RECOVERY VENTILATION UNIT OUTDOO R AIR TEMPERATURE
SETPOI NT
Only when AUX1 O = ERV
EXH1 SET 50% 0 to 100%;
Increment by 1
EXHAUST FAN STAGE 1 SETPOINT
SetpointforOAdamperpositionwhenexhaustfan1ispoweredbythe
economizer.
Wit h 2 ---speed fan uni ts Exh1 L (low speed fan) and Exh1 H (high speed
fan) settings are required. Default for Exh1 L is 65% and Exh1 H is 50%
EXH2 SET 75% 0 to 100%;
Increment by 1
EXHAUST FAN STAGE 2 SETPOINT
SetpointforOAdamperpositionwhenexhaustfan2ispoweredbythe
economizer. Only used when AUX1 O is set to EHX2.
Wit h 2 ---speed fan uni ts Exh2 L (low speed fan) and Exh2 H (high speed
fan) settings are required. Default for Exh2 L is 80% and Exh2 H is 75%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant 549J Series and is the answer not in the manual?

Bryant 549J Series Specifications

General IconGeneral
BrandBryant
Model549J Series
CategoryHeat Pump
LanguageEnglish

Related product manuals