EasyManuals Logo

Bryant 549J Series User Manual

Bryant 549J Series
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
8
C
D
A
B
C11247
LOCATION DIMENSION CONDITION
A
48--- in. (1219 mm)
18--- in. (457 mm)
18--- in. (457) mm
12--- in. (305 mm)
Unit disconnect is mounted on panel
No disconnect, convenience outlet option
Recommended service clearance
Minimum clearance
B
42--- in. (1067 mm)
36--- in. (914 mm)
Special
Surface behind servicer is grou nded (e.g., metal, masonry wall)
Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
Check sources of flue products within 10---ft of unit fresh air intake hood
C
36--- in. (914 mm)
18--- in. (457 mm)
Side condensate drain is used
Minimum clearance
D
42--- in. (1067 mm)
36--- in. (914 mm)
Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application
planning overhead obstruction or for vertical clearances.
Fig. 4 -- Service Clearance Dimensional Drawing
REFRIGERATION SYSTEM
COMPONENTS
Eac h heat pump refrigerat ion system includes a
compressor, accumulator, reversing valve, dual--function
outdoor coil with vapor header check valve, cooling liquid
line with a filter drier and a check valve, dual--function
indoor coil with a vapor header check valve, and heating
liquid line with check a valve and a strainer. Size 07 units
have a single compressor--circuit; unit size s 08 through 09
have two compressor--circ uits. See Fig. 5 for typical unit
piping schematic (unit size 09 (4--row indoor coil) with
two compressor--circuits is shown).
Dual--functi on outdoor a nd indoor coils are designed to
provide parallel coil circuits during evaporator--func tion
operation and converging coil circuits during the
condenser--function operation.
Reversing Valve and Check Valve Position
See Fig. 5 (on page 9) and Tables 1, 2, and 3.
Troubleshooting Refrigerant Pressure Problems and
Check Valves
Refer to Fig. 5 and the Cooling Mode and Heating Mode
tables (Tables 1 and 2).
Refrigerant System Pressure Access Ports
There are two access por ts in each circuit -- on the suctio n
tube and the discharge tube near the compress or. These are
brass fittings with black plastic caps. The hose connection
fittings are s tand ard
1
/
4
--in. S A E male flar e couplin gs.
The brass fittings are two--piece High Flow valves, with a
receptacle base brazed to the tubing and an integral
spring --closed check valve core screwed into the base. See
Fig. 6 on page 9. This check valve is permanently
assemble d into this core body and cannot be serviced
separately. Replace the entire c ore body if necessary.
Service tools are available from RCD that allow the
replacement of the check valve core without having to
recove r the entire system refrigerant charge. Apply
compressor refrigerant oil to the check valve core’s
bottom O--ring. Install the fitting body and torque to
96 10 in--lbs (10.9 1 Nm). Do not exceed 106 in-- lbs
(11.9 Nm) when tightening.
Table 1 Cooling Mode (each circuit)
Component Status/Position
Reversing Valve Energized
Check Valve A Closed
Check Valve B Open
Check Valve C Closed
Check Valve D Open

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant 549J Series and is the answer not in the manual?

Bryant 549J Series Specifications

General IconGeneral
BrandBryant
Model549J Series
CategoryHeat Pump
LanguageEnglish

Related product manuals