32
6.3.1.2. Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired
temperatures. The deadband does not change when the user changes between
Fahrenheit (_F) and Celsius (_C). Ex: A 2_ deadband will be 2_For2_Canddoes
not change with units, _Fand_C. This can allow one setting to “push” the other to
maintain this difference. When the correct deadband is set, touch SAVE.
S Deadband: Adjustable from 0 to 6_
d Default = 2_
6.3.1.3. Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and
humidity sensors. These offsets are added to the actual temperature/humidity
values. See also Section 6.3.8.2. When the correct offsets are made, touch SAVE.If
the system is non--zoned, the indoor temperature offset is found on this screen. If
the system is zoned, the indoor temperature offset is found in the Zoning, Offsets
screen.