EasyManua.ls Logo

Buchi Rotavapor R-220 Pro Continuous - 2 Electrical Connections

Buchi Rotavapor R-220 Pro Continuous
90 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Putting into operation
31 R-220 Pro Continuous Operation Manual, Version A
NOTICE
Risk of instrument damage by liquids or mechanical shocks.
Do not spill liquids over the instrument or its components
Do not move the instrument when it is loaded with sample liquid
Do not drop the instrument or its components
Keep external vibrations away from the instrument
Safely attach the instrument to the bench in earthquake prone regions
Do not operate the instrument without the protection cover installed at the front
NOTE
Secure the instrument against tilting and unintentional moving in earthquake prone regions.
5.2 Electrical connections
The Rotavapor
®
is aimed to be installed stationary and is not equipped with a power plug. The elec-
trical installation must be performed by an electrician or equivalent specialist in any case. After the
installation procedure an electrical safety test must be performed to verify a safe system condition
such as sucient grounding.
Mobile / stationary installation
In mobile mode the instrument is connected to mains via a power plug. The plug must be freely
accessible at any time to be unplugged in case of emergency.
In case the instrument is installed stationary (without power plug) an emergency power-o device
must be installed in the vicinity of the Rotavapor® with free access granted.
Demands on the mains circuit
The mains circuit must
provide the voltage that is given on the type plate of the instrument.
be able to handle the load of the connected instruments.
be equipped with adequat fusage and electrical safety measures, in particular proper grounding.
For details about the installation requirements, see "Installation Instruction R-220 Pro" document.
See also technical data (section 3.2) of all components regarding the dierent minimum system
requirements!
NOTE
Additional electrical safety measures such as residual current breakers may be necessary to meet
local laws and regulations!
External power switches (e.g. emergency stop switches) must meet IEC 60947-1 and IEC
60947-3 requirements. Such devices must be clearly labeled and accessible at any time.
External connections and extension lines must be provided with a grounded conductor lead
(3-pole couplings, cord or plug equipment). All used power cords must meet the input power
requirements.

Table of Contents

Related product manuals