EN
You have purchased a product that is durable and
easy to service.
However, all technical equipment requires regular
servicing in order to guarantee optimal functionality.
The operator must perform a visual check and
backwashtheltertoguaranteefunctionalityand
fullthewarrantyconditions.
According to DIN EN 806-5, the filter must be
checkedfor leaks anddirt every sixmonths and
backwashed at regular intervals, which may depend
on operating conditions but must be no longer than
sixmonths.
Wearing parts must also be replaced within the
prescribed maintenance intervals in order to ensure
functionalityandfullthewarrantyconditions.
The BWTafter-sales service sta or an installer
authorised by BWT must carry out the following
maintenance work regularly.
Water pressure dropped
considerably in network
Dirtylterelement Carryoutbackwash
Flushing water outlet does
not close
Backwash element does not reach
the end position due to large par-
ticles of dirt
Repeat backwash several times
Pullcoverplate(8)downandclose
ushingwateroutletwithsafetystop
valve(7).
Flushing water outlet leaks Defective seal Havesealreplacedbyspecialistrm.
Ifthefaultcannotberectiedusingthesenotes,pleasecontactaspecialistrmorourCustomerService.
Flat gasket Every 3 years
Stopper Every 3 years
Filter element Every 6 years
Backwashelement(repairkit) Every6years
Oring(inbayonet) Every15years
Transparent cylinder Every 15 years
We recommend that you enter into a maintenance
agreement with your installer or the after-sales
service team.
Plasticpartsmustonlybecleanedwithasoft,damp
cloth; do not use any solvents, detergents or acid
cleaners.
In the event of a failure during the warranty period,
pleasecontactourCustomerServiceDepartment,
quoting the equipment type and the PNR = pro-
duction number (see technical data or rating plate
onequipment).
WarrantyworkmayonlybecarriedoutbyourCus-
tomer Service Department.
Warranty workby a specialist rm requires the
expressconsentofourCustomerServiceManager.