SHOW DUPLICATE ADDRESSES
This function helps to locate devices with duplicate (double) addresses by activating their device
(polling) LEDs.
If there is a duplicate address a fault may have been displayed at the panel stating, ‘Loop configuration
has changed on Loop 1’, ‘There are faults on this zone’.
Press More Information button, then press the
5and6scroll buttons to view additional information
on the fault.
To show light the LEDs of the duplicate addresses enter AL3 (4444) > Commissioning Functions >
Address Functions > Show Duplicate Addresses.
When the SHOW DUPLICATE DEVICES prompt is displayed press the Accept
4button and details of the
double address will appear, for example:
Press the Accept
4button and the LEDs of the devices with duplicate addresses will be lit steady red.
To fix the duplicate address at the panel, press Escape
3 button and go to FIX DUPLICATE ADDRESS
function (see page 29).
To switch off the device LEDs, press the Accept
4button again as shown below.
Loop: 1 Device 8 : Duplicate Address
Turn ON device LED?
Loop: 1 Device 8 : Duplicate Address
Turn OFF device LED?
CAST XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENGINEERING MANUAL • Approved Document No. DFU5010000 Rev 4 • Page 28 of 48