F 41 M2 motor's opening slow-
down point
10 = 10% of the travel / … / 25 = 25% of the travel (default) / … / 60 = 60% of the travel
Adjusting as a percentage of the total travel, the M2 motor's opening slow-down starting point.
This function only appears if the Encoder function is activated.
F 42 M2 motor's closing slow-
down point
10 = 10% of the travel / … / 25 = 25% of the travel (default) / … / 60 = 60% of the travel
Adjusting as a percentage of the total travel, the M2 motor's closing slow-down starting point.
This function only appears if the Encoder function is activated.
F 43 M2 motor's opening
approach point
1 = 1% of the travel /… / 10 = 10% of the travel (default)
Adjusting as a percentage of the total travel, of the M2 motor's opening approach starting point.
This function only appears if the Encoder function is activated.
F 44 M2's closing approach
point
1 = 1% of the travel /… / 10 = 10% of the travel (default)
Adjusting as a percentage of the total travel, the M2 motor's closing approach starting point.
This function only appears if the Encoder function is activated.
F 46 Number of motors 0 = M1 and M2 (default) / 1 = M2
For setting the number of motors connected to the control panel.
F 49 Managing the serial
connection
0 = Deactivated (default) / 3 = CRP
To enable functioning of the Came Remote Protocol.
F 50 Saving data 0 = Deactivated (default) / 1 = Activated
Saving users and saved settings in memory roll.
This feature only appears if a memory roll has been fi tted into the control board.
F 51 Read data 0 = Deactivated (default) / 1 = Activated
Uploading data saved in memory roll.
This feature only appears if a memory roll has been fi tted into the control board.
F 56 Peripheral number 1 ----> 225
To set the peripheral's number from 1 to 255 for each control board when you have a system with several operators.
F 63 Changing COM speed 0 = 1200 Baud / 1 = 2400 Baud / 2 = 4800 Baud / 3 = 9600 Baud / 4 = 14400 Baud / 5 = 19200 Baud
/ 6 = 38400 Baud / 7 = 57600 Baud / 8 = 115200 Baud
For setting the communication speed used in the CRP (Came Remote Protocol) connection system.
F 65 Wireless input RIO-EDGE
[T1]
0 = Deactivated (default) / 7 = P7 / 8 = P8
RIO-EDGE wireless safety device associated to any function chosen among those available: P7 = reopening during closing, P8 = reclosing during
opening.
For programming, see the instructions that come with the accessory.
This function only appears is the control board has been fi tted with a RIO-CONN card.
F 66 Wireless input RIO-EDGE
[T2]
0 = Deactivated (default) / 7 = P7 / 8 = P8
RIO-EDGE wireless safety device associated to any function chosen among those available: P7 = reopening during closing, P8 = reclosing during
opening.
For programming, see the instructions that come with the accessory.
This function only appears is the control board has been fi tted with a RIO-CONN card.
F 67 Wireless input RIO-CELL
[T1]
0 = Deactivated (default) / 1 = P1 / 2 = P2 / 3 = P3 / 4 = P4
RIO-CELL is associated to any function chosen among those available: P1 = reopening during closing; P2 = reclosing during opening; P3 = partial
stop; P4 = obstruction wait.
For programming, see the instructions that come with the accessory.
This function only appears is the control board has been fi tted with a RIO-CONN card.
F 68 Wireless input RIO-CELL
[T2]
0 = Deactivated (default) / 1 = P1 / 2 = P2 / 3 = P3 / 4 = P4
RIO-CELL is associated to any function chosen among those available: P1 = reopening during closing; P2 = reclosing during opening; P3 = partial
stop; P4 = obstruction wait.
For programming, see the instructions that come with the accessory.
This function only appears is the control board has been fi tted with a RIO-CONN card.