M1 - 24 V DC gearmotor featuring delayed action on opening
M2 - 24 V DC gearmotor featuring delayed action on closing
Safety devices
Confi gure either (N.C.) contacts CX, CY or CZ, input
for safety devices such as photocells, that comply with
EN 12978 standards. See CX, CY or CZ input functions
in:
- C1 «re-open during closing phase», When the
gate leaf is closing, opening the contact triggers the
inversion of the direction of movement until the gate
leaf is fully open.
- C2 «re-close during opening phase», When gate
is opening, if the contact is opened it triggers an
inversion of the direction until gate is fully closed;
- C3 «partial stop», Halts moving gate leaves and
causes them to automatically close (if this functions
has been selected);
- C4 «stand-by Obstacle», Halts the moving gate
leaves causing them to start moving again once
obstacle is removed.
- Deactivated, if contact is unused.
DIR photocells
DOC photocells
Gearmotor, mechanical stops
Gearmotor, encoder
M1 - 24 V DC gearmotor featuring delayed action on opening
M2 - 24 V DC gearmotor featuring delayed action on closing
White
Brown
Green
Green
Brown
White