Campbell CR1000X - Status Table System Information and Settings (Continued)

Campbell CR1000X
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Keyword Information and Location
PortConfig
Provides information on the configuration settings (input, output, SDM,
SDI-12, COM port) for C terminals in numeric order of terminals. Default =
Input. Updates when the port configuration changes.
l String data type
l Read only
PortStatus
States of C terminals configured for control. On/high (True) or off/low
(False). Array elements in numeric order of C terminals. Default = False.
Updates when state changes.
l Boolean data type
ProcessTime
Processing time (μs) of the last scan. Time is measured from the end of the
EndScan instruction (after the measurement event is set) to the beginning
of the EndScan (before the wait for the measurement event begins) for the
subsequent scan. Calculated on-the-fly. Updated at the conclusion of
scan processing, prior to waiting for the next scan.
l Numeric data type
l Read only
ProgErrors
Number of compile or runtime errors for the running program. Updated
after compile.
l Numeric data type
l Read only
ProgName
Name of current (running) program; updates at startup.
l String data type
l Read only
ProgSignature
Signature of the running CRBasic program including comments. Does not
change with operating-system changes. Updates after compiling the
program.
l Numeric data type
l Read only