datalogger, connect to it in Device Configuration Utility, click the Backup menu and select
Backup Datalogger.
Table 5-1: Powerup.ini commands
Command Action Details
1
Run always,
preserve data
Copies a program file to a drive and sets the program to both
Run Now and Run on Power Up. Data on a memory card from
the previously running program will be preserved if table
structures have not changed.
2
Run on
power up
Copies a program file to a drive and sets the program to Run
Always unless command 6 or 14 is used to set a separate Run
Now program.
5 Format Formats a drive.
6
Run now,
preserve data
Copies a program file to a drive and sets the program to Run
Now. Data on a memory card from the previously running
program will be preserved if table structures have not
changed.
7
Copy
support files
Copies a file, such as an Include or program support file, to
the specified drive.
9
Load OS
(File= .obj)
Loads an .obj file to the CPU drive and then loads the .obj
file as the new datalogger operating system.
13
Run always,
erase data
Copies a program to a drive and sets the program to both Run
Now and Run on Power Up. Data on a memory card from the
previously running program will be erased.
14
Run now,
erase data
Copies a program to a drive and sets the program to Run Now.
Data on a memory card from the previously running program
will be erased.
15 Move file
Moves a file, such as an Include or program support file, to the
specified drive.
5.6.2 Example powerup.ini files
Comments can be added to the file by preceding them with a single-quote character ('). All text
after the comment mark on the same line is ignored.