EasyManuals Logo

Carel IR33E9HR20 User Manual

Carel IR33E9HR20
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
32
ENG
ir33 universale +030220801 - rel. 2.1 - 21.06.2011
The “activation” parameter is expressed as a percentage, from -100 to +100
and refers to the operating di erential and the set point that the output
refers to. If the output refers to St1 (“dependence”=1), “activation is relative
to the percentage value of P1; if the output refers to St2 (“dependence”= 2),
activation” is relative to the percentage value of P2.
If the value of “activation is positive, the activation point is to the ‘right of the
set point, while if negative it is to the ‘left’.
If dependence”=15 & “type of output”=1, the “activation parameter
de nes the ON time as a percentage of the period (c12); in this case,
activation” must only have positive values (1 to 100).
Example 1:
The  gure below shows the activation points on a controller with 2
outputs, with the following parameters:
St1=10, St2=20, P1=P2=6
OUT1 (point A): dependence”=c34=1, “activation”= c36=-100;
OUT2 (point B): dependence”=c38=2, “activation”= c40= +75.
A=4; B=24.5
St1=10
c36=-100
St2=20
c40=+75
OUT1
AB
OUT2
B1
P1=6 P1=6 P2=6 P2=6
ON
OFF
Fig. 5.m
Key
St1/2 Set point 1/2
P1 Di erential for output 1
P2 Di erential for output 2
OUT1/2 Output 1/2
B1 Probe 1
Example 2
A timer output is selected with dependence”=15, “type of output”=1
and “activation” (ON percentage) between 1 and 100, with a cycle time
set by c12. Below OUT1 and OUT2 are proposed as “timer outputs with
c36 greater than c40, example:
OUT1: c34=15, c35=1, c36=50; OUT2: c38=15, c39=1, c40=25.
ON
OUT1
OUT2
OFF
t
c12
TON_2
ON
OFF
c12
TON_1
Fig. 5.n
Key
t time
c12 cycle time
OUT1/2 Output 1/2
TON_1 (c36*c12)/100
TON_2 (c40*c12)/100
5.6.4 Di erential/logic ( parameters c37,c41,c45,c49)
The “di erential/logic” parameter is only active if the output is the control
output (“dependence”=1,2,16,17). Like the “activation parameter, it is
expressed as a percentage and is used to de ne the hysteresis of the
output, that is, for ON/OFF operation, the deactivation point of the output
or, for PWM operation, the point where the output has the minimum value
(ON time =0). If the output refers to St1 (“dependence”=1), di erential/
logic” is relative to the percentage value of P1; if the output refers to St2
(“dependence”= 2), di erential/logic” is relative to the percentage value
of P2. If the value of di erential/logic” is positive, the deactivation point is
greater than the activation point and “reverse logic is created.
If the value of di erential/logic” is negative, the deactivation point is less
than the activation point and direct logic is created.
Together with the previous “activation” parameter, this identi es the
proportional control band.
Example 3.
Example 3 completes example 1, adding the deactivation points.
For the  rst output “reverse operation is required, and the di erential P1;
for the second, direct logic and the di erential equal to half of P2.
The parameters are :
Output 1 : di erential/logic”=c37=+100 (A’)
Output 2: ”di erential/logic”=c41=-50 (B’)
A’=10; B’=21.5
c36=-100
c37=+100
c41=-50
c40=+75
OUT1
AA B’B
OUT2
B1
P1=6 P1=6 P2=6 P2=6
St1=10 St2=20
ON
OFF
Fig. 5.o
Key
St1/2 Set point 1/2
c36/c40 Activation of output 1/2
c37/c41 Di erential/logic for output 1/2
OUT1/2 Output 1/2
P1 Set point di erential 1
P2 Set point di erential 2
B1 Probe 1
As an example, reversing the values of di erential/logic”, the new
deactivation points are as follows
Output 1 : di erential/logic”=c37=-50(A’)
Output 2: ”di erential/logic”=c41=+100 (B’)
A’=1; B’=30.5
c36=-100
OUT1
A’’ A B
B’
OUT2
B1
P1=6 P1=6 P2=6 P2=6
St1=10 St2=20
ON
OFF
c40=+75
c41=+100
c37=-50
Fig. 5.p
5.6.5 Activation restriction (par. d34,d38,d42,d46)
In normal operating conditions, the activation sequence should be as
follows: 1,2,3,4. However, due to minimum on/o times or times between
successive activations, the sequence may not be observed. By setting
this restriction, the correct sequence is observed even when timers have
been set. The output with the activation restriction set to ‘x (1,2,3) will

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel IR33E9HR20 and is the answer not in the manual?

Carel IR33E9HR20 Specifications

General IconGeneral
BrandCarel
ModelIR33E9HR20
CategoryControl Unit
LanguageEnglish

Related product manuals